Complete Guide to Ventilation and Cooling Pad System Design for Broiler Farms

▼Add:Intersection of Lijiang Road and Wenchang Road in New Area, Hua County, Henan, China

✉Email:marketing@sdeley.com

☎WP:+8613151616621

▶Web:sdeley.net

Scientific Calculation of Air Exchange & Equipment Configuration

I. Scientific Calculation of Air Exchange Requirements

1. Air Exchange Standards

The international standard is based on ​ventilation volume per unit body weight, with differentiation by growth stage:

  • Minimum Requirement: 1.0 m³/h/kg (basic air quality maintenance)
  • Maximum Requirement: 7.0 m³/h/kg (extreme heat or high-density farming)
  • Common Practice: 4.0 m³/h/kg (adult broilers at 2.5kg body weight)

Note: Apply a ​1.2~1.4x safety factor​ to compensate for theoretical deviations.

2. Air Exchange Formula

M=A×W×Mv

  • Parameters:
    • M: Total air exchange (m³/h)
    • A: Stocking capacity (e.g., 30,000 birds)
    • W: Body weight (2.5kg/adult, 1.0kg/chick)
    • Mv​: Ventilation rate per kg (1.0~7.0 m³/h/kg)

Example:
Max requirement = 30,000 × 2.5kg × 7.0 m³/h/kg = ​525,000 m³/h


II. Dynamic Ventilation Management

1. Seasonal Strategies
SeasonAir Exchange TimePurpose
Hot≤1 minuteRapid cooling, reduce heat accumulation
Moderate≤2 minutesBalance humidity & energy use
Cold≤3 minutesMaintain temperature + minimum air exchange
2. Ventilation Volume Formula

V=L×W×H×60

  • Parameters:
    • V: Required ventilation (m³/h)
    • L,W,H: House length/width/height (e.g., 100m×12.5m×4m)

Example:
Base ventilation = 100m × 12.5m × 4m × 60 = ​300,000 m³/h


III. Critical Equipment Configuration

1. Fan Quantity Calculation
fan

N=Q×BV1​×n

  • Parameters:
    • N: Fan units
    • V1​: House volume (12.5m×4m×100m = 5,000m³)
    • n: Air changes/hour (60 for extreme conditions)
    • Q: Fan capacity (e.g., 43,500 m³/h)
    • B: Correction factor (0.6)

Example:
Max fans = (5,000m³ × 60) ÷ 43,500 ÷ 0.6 ≈ ​12 units

2. Cooling Pad Area
Cooling pad wall

C=D×3600Vv​​

  • Parameters:
    • C: Pad area (m²)
    • Vv​: Max ventilation (525,000 m³/h)
    • D: Air velocity through pads (1.5~2.0 m/s for 15cm thickness)

Example:
Pad area = 525,000 ÷ (1.5 × 3,600) ≈ ​97m²​ (recommended: 85m² mid-value)


IV. Optimization Tips

  1. Airflow Control:
    • Max in-house wind speed ≤2.92 m/s (avoid stress)
  2. Leakage Compensation:
    • Add 10%~15% fan/pad capacity for older houses
  3. Regional Adaptation:
    • Southern regions: Use upper limits (9 m³/h/kg)
    • Northern regions: Lower limits (5 m³/h/kg)

Case Study:
A 30,000-bird farm configuration:

  • Fans: 12 units (43,500 m³/h each)
  • Cooling Pads: 85m² (15cm thick, 1.8 m/s)
  • Efficiency: 525,000 m³/h (full air exchange in 1 minute)

Result: Ammonia <10ppm, summer temperature differential ≤3℃.